Outdoor Single Pole Fused Recloser by-Pass Switches 11kv

 
 
单价 11.00 / Piece对比
销量 暂无
浏览 68
发货 Chinahubeisuizhou
库存 7000Piece
过期 长期有效
更新 2020-08-18 10:54
 
联系方式
加关注0

ORIENT ELECTRIC INTERNATIONAL GROUP LIMITED

企业会员第4年
资料未认证
保证金未缴纳
详细说明
Product Name: Outdoor Single Pole Fused Recloser by-Pass Switches 11kv Model NO.: DSP-11/600 Brand: Oei Power Certification: IEC IEEE Structure of Operating: Manual Common Model: Ist Run: Turn the Horizontal Series: Three Grounding: Single Ground Number of Poles: Three Pole Movement Mode: Horizontal Rotary Type Grounding Mode: Grounding Operation: Manual Installation: Outdoor High-voltage Structure: Three-column Disconnector Type: High-voltage 12: Kv 24: Kv 36: Kv Trademark: OEI Power Transport Package: Wooden Case Specification: IEC IEEE Origin: China Nanyang HS Code: 8535309000 Product Description Center Break Isolator and double Break IsolatorThese disconnectors are , no load switching deviceswhich physically isolate the lines. They are designed forhorizontal outdoor application and can also be designedfor vertical installation. For earthing and closing ofswitchyard portions of the installation, the earthingswitches are provided on disconnector. If required.The following documents were referred to during the preparation of this specification. In case of conflict, the provisions of this specification shall take precedence.IEC 129:1975: Alternating Current Disconnectors (Isolators) and Earthing SwitchesIEC 60694:2002: Common Specifications for High Voltage Switchgear and ControlgearBS 729: Hot dip galvanized coating on iron and steel articlesIEC62271-102Isolator (Disconnector) - a mechanical switching device which provides, in the open position, an isolating distance in accordance with Electrical Safety requirements.SERVICE ConDITIONSThe isolator shall be suitable for continuous operation outdoors in tropical areas at altitudes of up to 2200m above sea level, humidities of up to 90%, average ambient temperature of +30ºC with a minimum of -1ºC and a maximum of +40ºC and heavy saline conditions along the coast.4.2. DESIGN AND CONSTRUCTION4.2.1 The Isolator, Solid link shall be designed and constructed in accordance with IEC 129 and IEC 60694.4.2.2 The isolating link shall be of the vertical opening, designed for single phase manual operation. It shall be easily removed and replaced by using a portable operating rod.4.2.3 The isolating link shall incorporate double porcelain insulators to suit voltage requirements and mounted on hot dipped galvanised steel under base suitable for vertical mounting.4.2.4 The isolating link shall be arranged so that each unit is mounted independently on an angle bracket. It shall be supplied complete with the angle bracket and accessories suitable for mounting on 'U' type steel channel. The drawings to be submitted shall indicate all the applicable mounting positions.4.2.5 The isolator shall be designed such that in fully open position, it shall provide adequate electrical isolation between the contacts on each phase. It shall conform to the requirement as single point isolation for safety.4.2.6 All steel parts shall be hot dip galvanized to BS 729. The minimum coating of galvanizing required is 80 microns.4.2.7 The solid link shall be removable from the mounting by use of operating rod.4.2.8 All current carrying parts of the isolator shall be made of high conductivity material.4.2.9 The isolator shall be fitted with clamp connectors for Aluminium (ACSR) conductor ofAluminium (ACSR)conductor of up to 18.2mm diameter.The rating of the complete isolator shall be as follows: -Rated voltage36 kVRated frequency50 HzRated lightning impulse withstand voltage200 kVRated power frequency withstand voltage, dry95 kVRated normal current400 AmpsRated short time withstand current for 3 sec, min.18.0 kAMinimum creepage distance of insulators900 mmSOLID linkS 11KVN/ODETAILDATA1DescriptionSolid link assembly complete with linkrated at 200A and mounting bracket to PIESA 002. (See Figure 1 to Figure 12 below)2System conditions of servicea) nominal Voltage (Un) r.m.skV11b) maximum system voltage (Um) r.m.sKV12c) earthingEffective & non effectived) FrequencyHz503Site conditions of servicea) altitudem1400b) Operating Ambient temperature°C-1 to 40c) Humidity%854Ratinga) Nominal voltagekV11b) Rated currentSolid linkA200Cut out baseA2005Electrical componentsa) Insulator material specificationPorcelainDielectric strengthLightning impulse withstand (1.2/50)kV95Power frequency wet withstand voltager.m.skV286Specific creepage distancemm/kV257General information to be providedwith bid:Drawings and brochures showing outline and general arrangementYes/NoYesb) Detailed drawings of all itemsshowing critical tolerances to be provided with bidYes/NoYes8Previous Type test report/certificate oncomplete solid link assembly to be provided with bidYes/NoYes10Routine tests (acceptance tests onsampleProduct) to be provided on deliveryYes/NoYes11Applicable standardPIESA 00212Other applicable standardsNRS 035SABS IEC 60282-2SABS IEC 60186BS 137 part 2TRI-linkSLot 3-(a) 11kV with interruptersN/ODETAILDATA1TYPE11kV pre-assembled gangoperated overhead line load break switch complete with expulsion interrupters2Mounting configurationHorizontal3Mode of operationManually operated polemounted linking rod and handle with locking facilitiesa) nominal Voltage (Un) r.m.skV11b) maximum voltage (Um) r.m.sKV12c) earthingEffective & non effectived) FrequencyHz50e) rated currentAmp400f) Fault closing capacitykA12.54Site conditions of servicea) altitudemetres1400b) Operating Ambient temperature°C-1 to +40c) Relative humidity%855Electrical componentsa) Insulator material specificationHigh Temperature VulcanisedSilicon rubberb) Cross arm and operating controls materialsHot dip galvanized steel toSAN760Dielectric strengthLightning impulse withstand (1.2/50)kV95Power frequency wet withstand voltage r.m.sKV28Short time current rating -1seckA12.56creepage distancemm/kV257General information to be provided with bid:Drawings and brochures showingOutline and general arrangementYes/NoYes8Previous Type test report/certificate on completeassembly to be provided with bidYes/NoYes.9Routine tests (acceptance tests on sampleProduct) to be provided on delivery.Yes/NoYes10Applicable standardsIEC62271FURTHER REQUIREMENTS:Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring-loaded mechanisms.All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.SUPPLIMENTARY NOTESSuppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to customer, It is therefore imperative that schedule "B" is completed by the tenderer. Any deviations/modifications/alternatives specification must be listed in schedule "C.33kV with interruptersN/ODETAILDATA1TYPE33kV pre-assembled gangoperated overhead line load break switch complete with expulsion interrupters2Mounting configurationHorizontal3Mode of operationManually operated polemounted linking rod and handle with locking facilitiesa) nominal Voltage (Un) r.m.skV33b) maximum voltage (Um) r.m.sKV36c) earthingEffective & non effectived) FrequencyHz50e) rated currentAmp200f) Fault closing capacitykA12.54Site conditions of servicea) altitudemetres1400b) Operating Ambient temperature°C-1 to +40c) Relative humidity%855Electrical componentsa) Insulator material specificationHigh Temperature VulcanisedSilicon rubberb) Cross arm and operating controls materialsHot dip galvanized steel toSAN760Dielectric strengthLightning impulse withstand (1.2/50)kV170Power frequency wet withstand voltage r.m.sKV70Short time current rating -1seckA12.56creepage distancemm/kV257General information to be provided with bid:Drawings and brochures showingOutline and general arrangementYes/NoYes8Previous Type test report/certificate on completeassembly to be provided with bidYes/NoYes9Routine tests (acceptance tests on sampleProduct) to be provided on deliveryYes/NoYes10Applicable standardsIEC62271FURTHER REQUIREMENTS:Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring-loaded mechanisms.All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.SUPPLIMENTARY NOTESSuppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to custoemr.11kV without interruptersN/ODETAILDATA1TYPE11kV pre-assembled gangoperated overhead line switch without expulsion interrupters (non-load break switch)2Mounting configurationHorizontal3Mode of operationManually operated polemounted linking rod and handle with locking facilitiesa) nominal Voltage (Un) r.m.skV11b) maximum voltage (Um) r.m.sKV12c) earthingEffective & non effectived) FrequencyHz50e) rated currentAmp4004Site conditions of servicea) altitudemetres1400b) Operating Ambient temperature°C-1 to +40c) Relative humidity%855Electrical componentsa) Insulator material specificationHigh Temperature VulcanisedSilicon rubberb) Cross arm and operating controls materialsHot dip galvanized steel toSAN760Dielectric strengthLightning impulse withstand (1.2/50)kV95Power frequency wet withstand voltage r.m.sKV28Short time current rating -1seckA12.56creepage distancemm/kV257General information to be provided with bid:Drawing and brochures showingOutline and general arrangementYes/NoYes8Previous Type test report/certificate on completeassembly to be provided with bidYes/NoYes9Routine tests (acceptance tests on sampleProduct) to be provided on deliveryYes/NoYes10Applicable standardsIEC62271FURTHER REQUIREMENTS:Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring-loaded mechanisms.All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.SUPPLIMENTARY NOTESSuppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to33kV without interruptersN/ODETAILDATA1TYPE33kV pre-assembled gangoperated overhead line switch without expulsion interrupters (non-load break switch)2Mounting configurationHorizontal3Mode of operationManually operated polemounted linking rod and handle with locking facilitiesa) nominal Voltage (Un) r.m.skV33b) maximum voltage (Um) r.m.sKV36c) earthingEffective & non effectived) FrequencyHz50e) rated currentAmp2004Site conditions of servicea) altitudemetres1400b) Operating Ambient temperature°C-1 to +40c) Relative humidity%855Electrical componentsa) Insulator material specificationHigh Temperature VulcanisedSilicon rubberb) Cross arm and operating controls materialsHot dip galvanized steel toSAN760Dielectric strengthLightning impulse withstand (1.2/50)kV170Power frequency wet withstand voltage r.m.sKV70Short time current rating -1seckA12.56creepage distancemm/kV257General information to be provided with bid:Drawing and brochures showingOutline and general arrangementYes/NoYes8Previous Type test report/certificate on completeassembly to be provided with bidYes/NoYes9Routine tests (acceptance tests on sampleProduct) to be provided on deliveryYes/NoYes10Applicable standardsIEC62271FURTHER REQUIREMENTS:Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring-loaded mechanisms.All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.SUPPLIMENTARY NOTESSuppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to.
举报收藏 0
更多>本企业其它产品
10kv Cast Resin Dry Typehigh Voltage Power Electric Toroidal Transformer Gw9 -12/630 Series Hv Outdoor High Voltage Disconnect /Switch Isolator Outdoor Sf6 Gas Circuit Breaker 33kv Auto Recloser Circuit Breaker Disconnect Switch Isolator Single-Pole 600A Lightning Arrester  Surge Arrester  Pararrayos  Parafoudre 3-132kv  10ka Meter Box Isoladores De Porcelana P-33y Polymer Insulator
网站首页  |  关于我们  |  联系方式  |  用户协议  |  隐私政策  |  版权声明  |  网站地图  |  排名推广  |  广告服务  |  积分换礼  |  网站留言  |  RSS订阅  |  违规举报